UPS Systeme electric Smart – Save Online SRTSE6KRTXLI-NC

#9111570

UPS Systeme electric Smart – Save Online SRTSE6KRTXLI-NC

[double conversion, 6000 VA, 6000 W, terminal block, EPO, RS-232, SNMP slot, USB] details

Not on sale

  • Characteristics
  • Feedback 0
  • Instructions and files

Characteristics UPS Systeme electric Smart – Save Online SRTSE6KRTXLI-NC

General parameters

Type
UPS
Model
Systeme electric Smart – Save Online SRTSE6KRTXLI-NC
Main Color
black
Type
double conversion
Form Factor
Rack/Tower
Power Cable Length
0 m

Technical parameters

Maximum Output Power
6000 VA
Effective Power Output
6000 W
Minimum Input Voltage
176 V
Max Input Voltage
300 V
Min Input Frequency
40 Hz
Max Input Frequency
70 Hz
Output Voltage Stability
± 1 %
Minimum Output Frequency
46 Hz
Max Output Frequency
54 Hz
Wave Form
pure sine wave
Runtime
6.17 min (6000W)
Delay When Switching to Battery
0 ms

Connectors

Number and Type of Power Output Connectors
terminal block
Number of Power Output Connectors (UPS)
1
Connectors/Ports
USB, RS-232, EPO, SNMP slot
Port Layout
rack-mounted

Battery

Battery Type
lead-acid
Charging Time
4.5 h
Replaceable Batteries
yes
External Battery Connection
yes
Battery Included
yes

Additional Information

Housing Protection Class
IP20
Functions and Modes
emergency power-off (EPO), ECO mode, bypass
Cold Start
none
Display
LCD display
LED Indicators
mains power, overload, AC power input, discharge timer, malfunction, bypass mode, battery level, AC power output, voltage level, battery-powered, low battery level
Sound Signals
UPS fault (error), overload, low battery level, battery-powered
Noise Level
58 dB
Operating Temperature
from 0 to +40°C
Package Contents
shared-current cable, UPS parallel connection cable, removable support feet, cable for connecting external batteries, RS-232 cable, documentation, USB cable

Dimensions and Weight

Depth
610 mm
Width
438 mm
Height
221 mm
Weight
78 kg

Description

The Systeme electric Smart – Save Online SRTSE6KRTXLI-NC double-conversion UPS in a Rack/Tower form factor is equipped with a terminal block. The apparent output power and active power of the model are 6000 W. The device supports a wide input voltage range from 176 to 300 V.
The Systeme electric Smart – Save Online SRTSE6KRTXLI-NC UPS is designed for connecting external batteries. The backup runtime at a 6000 W load is 6.17 min. The model's package includes a USB cable, an RS-232 cable, an external battery connection cable, a UPS parallel connection cable, a shared current cable, and removable support feet.